4-Noks Meters & Sensors

Follow

In this article, the following topics are going to be addressed:

 

Configuration of 4-Noks devices

In this section, the following topics are going to be addressed:

 

Assign addresses to 4Noks Devices

There are two systems to assign addresses to 4Noks devices:

 

Binary Switch

Most 4Noks devices use a switch system to determine their address. Each switch represents a bit of the binary address being the left switch the Less Significant Bit. Do not use addresses smaller than 16.
Address = Switch1*1 + Switch2*2 + Switch3*4 + Switch4*8 + Switch5*16 + Switch6*32 + Switch7*64 + Switch8*128.


Examples:

01_2f68f8d6ec3a561aee98c934bdc870ac76b14f58728eb2981606584d6345c72b.png

 

Other devices

Some 4-Noks devices do not have a switch to set the address and the configuration is made using either a Z-HANDZER device or manually sending Modbus commands.
 

Z-HANDZER

Follow these steps:

  1. Turn the Z-HANDZER on.
  2. Select "Join Netw":
    02_2f68f8d6ec3a561aee98c934bdc870ac76b14f58728eb2981606584d6345c72b.png
  3. Select "Commands":
    03_29b2cdcd52bd74cfd33775a068fe0c5dff8f4434baacb64c1bcfb833991f07e1.png
  4. Select "Sens Menu":
    04_35e4a610b7349b3cbd20b420f569ad11f6f0fdc5942819622c493f07815fd327.png
  5. Select "Set Address":
    05_5810477b566aa702f19d0126da6fa3a05e084d22ef526da512fe9fa13fc7823e.png
  6. You're done

 

Modbus Commands (advanced users only)

To be able to change the address, you need to send 3 messages:

  1. Read Input register 0 of address 127.* 
  2. Write 6521 to Holding register 0 of address 127.
  3. Write X to Holding register 2 of address 127 (where X is the new address we want to use, 23 for example).
  4. Write 1 to Coil 0 of address 127.
  5. Read Input register 0 of address X (where X is the address set in step 3).*

* Not really necessary but it is useful to check the connectivity with the device.

 

Change frequency of 4Noks Devices

Modbus Commands (advanced users only)

To be able to change the frequency you need to send the following messages:

  1. Read holding register 1 of the device.* 
  2. Write the new frequency (in seconds) to the holding register 1.
  3. Read holding register 1 of the device to verify that the change has been successful.

* Not really necessary but it is useful to check the connectivity with the device.

 

4-Noks Meters/Sensors

List of 4noks meters/sensors that are compatible with DEXGate or DEXGate 2:

 Manufacturer's website: www.4-noks.com

 

4-Noks ZED-THI-M

1039fa4bc846ac5a7147cc8ca1827ba4a2314a5ad143bdcf263c241ca84d2544.jpeg
Manufacturer: 4noks (www.4noks.it)
Product and variants: ZED-THI-M
Description: The 4-Noks ZED-THI-M is an indoor/outdoor (IP 55) battery-powered device that performs temperature and humidity measurements at the same time.
Measures: Temperature, Humidity
Compatible using: DEXGate, Satel Owasys, EGX-300

Comments:

  • Modbus address is set using a DIP switch

(check the attached file: ZED-THI_UserManual)

 

4-Noks ZED-THL-M

06_4001a3039cb8f6b01c648b020f6e7259eb158433eeff4f75fbadaeae1f31d1da.jpeg
Manufacturer: 4noks (www.4noks.it)
Product and variants: ZED-THL-M
Description: The 4-Noks ZED-THL-M is an indoor/outdoor (IP 55) battery-powered device that reads
Measures: Temperature, Humidity, Light
Compatible using: DEXGate, Satel Owasys, EGX-300

Comments:

  • Modbus address is set using a dip switch

(check the attached file: ZED-THL_UserManual)

 

4-Noks ZED-TID-M

07_8fc2d68ddac29560e59ad86f45372c00c41866bc8c0141d0a5787fbcf2a15767.jpeg
Manufacturer: 4noks (www.4noks.it)
Product and variants: ZED-TID-M
Description: Indoor/outdoor (IP 55) battery-powered NTC probe data logger with digital inputs
Measures: Digital inputs and NTC probes
Compatible using: DEXGate, Satel Owasys, EGX-300

Comments:

  • Modbus address is set using a dip switch

(check the attached file: ZED-TID_UserManual)

 

4-Noks ZED-TIDCI-M

08_8fc2d68ddac29560e59ad86f45372c00c41866bc8c0141d0a5787fbcf2a15767.jpeg
Manufacturer: 4noks (www.4noks.it)
Product and variants: ZED-TIDCI-M
Description: Indoor/outdoor (IP 55) battery-powered pulse counter and NTC probe data logger
Measures: Digital pulses and NTC probes
Compatible using: DEXGate, Satel Owasys, EGX-300

Comments:

  • Modbus address is set using a dip switch

(check the attached file: ZED-TID-CI_manual)

 

4-Noks ZR-TIDCI-EM

10_4f2f4edb36f5fb383d6ce2b15c8a968632b4a3af0082a7650aa5ee12c3b0b7e9.jpeg
Manufacturer: 4noks (www.4noks.it)
Product and variants: ZR-TIDCI-EM
Description: Indoor 24V powered pulse counter and NTC probe data logger
Measures: Digital pulses and NTC probes
Compatible using: DEXGate, Satel Owasys, EGX-300

Comments:

  • Modbus address is set using a dip switch

(check the attached file: ZED-TID-CI_manual)

 

4-Noks ZR-TIDCI-OPT1

 

11_0d7304455ca451bce66d7bf7af8466152f8574019b5ccca343d9af481edf9e9a.jpeg
Manufacturer: 4noks (www.4noks.it)
Product and variants: ZR-TIDCI-EM
Description: Indoor 24V powered optical pulse counter
Measures: Optical pulses
Compatible using: DEXGate, Satel Owasys, EGX-300

Comments:

  • Modbus address is set using a dip switch.

(check the attached file: ZED-TID-CI_manual)

 

HMETER-3P / ZR-HMETER-3P

12_8559362f9b734b248b5976239c671a46b64fb740c069dbd082ea45870684ffd7.jpeg
 

Manufacturer: 4noks
Product and variants: HMETER-3P, ZR-HMETER-3P (50, 100 and 200 Amps versions)
Description: DIN-RAIL mount Three-phase power analyzer. Modbus RS485 and Zigbee versions.
Measures: Electrical parameters
Compatible using: DEXGate2
Comments: Zigbee version (ZR-HMETER-3P) requires a Zigbee gateway (ZC-GW-485-EM, ZC-GW-ETH-EM, or ZC-GW-ETH-EPM)

 

(check the attached file: ZR-HMETER3P-EM_Technical_Specs and ZR-HMETER3P_UserManual)

 HMETER-3P / ZR-HMETER-3P - Quick Install Guide

To follow this guide you will need:

Installation:

  1. Install the current transformers following the following diagram:

 ​​​13_52b3ef2e6c5632e20d6c89e0da97ae1004a6241f004be46b6370f1f438275662.png

  1. Connect the 17th terminal of the HMETER to the A(+) terminal in DEXGate2, the 18th terminal of the HMETER o the B(-) terminal in DEXGate2 and the 16th terminal of the HMETER to the S terminal in DEXGate2
14_48f3005fb766bc762cb32e24cb59ef61116532b36c55a44d2e2e2f2025474131.png
  1. Power up the meter
  2. Power up the DEXGate2
  3. Access the web administration interface of the DEXGate2 by connecting to its wifi access point and then enter (http://172.16.0.1)
  4. Login (the default username and password are admin/admin)
  5. Configure Modbus address on the device 

Default Modbus address is 127 and Baudrate is 9600. If you have only one HMETER you can use these values to connect to the device, without the need of changing its address or baudrate.

If necessary, Modbus Address has to be changed through RS485 by modifying certain registers. Look at the attached Quick Start Guide at section DEVICE ADDRESSING.
For further information on how to Modify these registers using DEXGate2 follow this tutorial.

  1. Go to the "Modbus Configuration" section
  2. Edit the configuration lines of the HMETER
  • For three-phase monitoring, edit the following lines adding the Modbus Address:
    • devices.fournoks-hmeter3p=
    • devices.fournoks-hmeter6p=
  • For single-phase monitoring, edit the following lines adding the Modbus Address:
    • devices.fournoks-hmeter3p-mono=
    • devices.fournoks-hmeter6p-mono=

Example: Lines should look like "devices.fournoks-hmeter6p=126,127" where 126 and 127 are addresses of two different devices.
 

  1. Save & restart the Modbus bridge or the DEXGate2.
  2. You're done!

 

HMETER-6P / ZR-HMETER-6P

15_288a486ab902e0054151461135a542066fa6879e7ba4181a7da771172eb600c0.png

Manufacturer: 4noks
Product and variants: HMETER-6P, ZR-HMETER-6P (50, 100 and 200 Amps versions)
Description: DIN-rail three-phase power analyzer (two three-phase channels). Modbus RS485 and Zigbee versions.
Measures: Electrical parameters
Compatible using: DEXGate2
Comments: Zigbee version (ZR-HMETER-6P) requires a Zigbee gateway (ZC-GW-485-EM, ZC-GW-ETH-EM, or ZC-GW-ETH-EPM)

Follow this Quick Install Guide.

 

 (check the attached file: ZR-HMETER-M_manual)

 

ZC-GW-ETH-EM / ZC-GW-ETH-EPM 

16_c3b16ce6e10f25959ce377aa03e5ab973cd1ab2cb4f7ad6ec368628e6d791014.png
 

Manufacturer: 4noks 
Product and variants: ZC-GW-ETH-EM, ZC-GW-ETH-EPM
Description: Zigbee to Ethernet Gateway. Connect Zigbee devices to Ethernet using Modbus-TCP.
Measures: Gateway
Compatible using: DEXGate2
 
(check the attached files: ZC-GW-ETH-EM__ZC-GW-ETH-EPM-Technical_Specs and ZC-GW-ETH-EM-Technical_Manual)
 

 

ZG-485-PW

17_7c2c5c37df3cbe5042f9993ea5413e74b8542dc3b3c46c50dfc41e7d9de32202.png

Manufacturer: 4noks 
Product and variants: ZG-485-PW
Description: Zigbee to RS485 Gateway. Connect Zigbee devices to a Modbus-RTU RS485 BUS.
Measures: Gateway
Compatible using: DEXGate2

NOTE: In case of adding some Zigbee devices like the ZR-HMETER, it is necessary to change the Working Mode of the gateway by writing the value 17 (default value is 21)  at the Holding Register [3]
 

Assign addresses to 4Noks Devices

(check the attached files: ZG-485-PW_UserManual Introduction zc-gw-485-em)

 

 

ZR-BR-485-EM

 

18_f07688c7392e04f31042c064c648be2a59fb8d09a28b8291c95e3daa05d8aa7e.png
 

Manufacturer: 4noks 
Product and variants: ZR-BR-485-EM
Description: RS485 to Zigbee Gateway. Connect Modbus-RTU devices to a Zigbee network.
Measures: Gateway
Compatible using: DEXGate2
 
(check the attached files: ZR-BR-485-EM-Technical_Specs and ZR-BR-485-M-Technical_Manual)

Was this article helpful?